INDIANA UNIVERSITY
CENTRAL HEATING PLANT
REPORT OF OPERATION FOR FISCAL YEAR 1996-97

STEAM PRODUCTION:

UNIT #1 343,820,000 Lb   UNIT #4 289,824,000 Lb

UNIT #2 101,269,000 Lb UNIT #5 426,211,000 Lb

UNIT #3 10,290,000 Lb     UNIT #6 375,622,000 Lb

Total Steam Production 1,547,036,000 Lb
Total Steam to Campus 1,258,514,000 Lb, 81.1 %
Total Steam to Auxil. 288,522,000 Lb, 18.6 %
Condensate Returned 351,135,000 lb. (27.9% of campus consumption)
City Water Used 132,320,500 Gal

FUEL DATA:

Remote Storage: 20,686 tons
On site mine coal 7/1/96: 5,926 tons, 6/30/97: 2,500 tons
On site reserve coal 7/1/96: 1,488 tons, 6/30/97: 1,488 tons
Coal delivered from remote storage: 0 tons
Coal delivered from mines: 55,761 tons
Coal burned: 55,306 tons (note: accounting/scales error of 3,881 tons)
Natural gas burned: 5,153,744 therms
#2 fuel-oil burned: 436 gallons

FEEDWATER TREATMENT CHEMICALS USED:

Chelant B-0003 30,940 Lb
Sulfite B-0004 5,120 Lb
Amine B-0002 43,016 Lb
Caustic Soda 9,898 Lb
Antifoam B-0005 685 Lb
Sulfuric Acid 159,740 Lb
Salt: 188 tons

ELECTRICITY CONSUMED:  4,859,200  kWH


Utilities Links
|
Utilities Home Page | Site Index |
|
Information | Mission Statement | Weather | History |
|
Reports | Projects | Outages | Map Location |
Last Updated: September 30, 2002

The Utilities web site is currently maintained by
VPAD Tech Support.  Please notify any changes or errors found.
Access to Stats Page
 


Physical Plant Links

| Information | Need Service Now? | Publications | Talk to Us | Links |
|
IU Homepage | Campus Pictures | PP Intranet | Organization Chart |
|
Physical Plant Home | Administrative Services | Building Maintenance |
|
Building Services | Campus Division | Electronics | Engineering | Utilities |